Transformer is a kind of electrical equipment for energy exchange. According to different structures and cooling and insulating media, it can be divided into the following three categories: oil-immersed power transformers, gas-insulated power transformers, and dry-type power transformers.
When the transformer oil level does not
conform to the oil temperature, that is, does not conform to the temperature
curve, it is judged that the oil level is abnormal. Abnormal oil level is
mainly manifested as false oil level and low oil level.
(1) Failure of the oil level indicator:
check and repair the oil level indicator.
(2) The respirator is blocked, so that air
cannot enter when the oil level drops, and the oil level indication is too
high: clear the respirator.
(3) Gas accumulates in the oil chamber of
the oil conservator, making the oil level higher than the actual oil level: the
oil conservator must be filled and exhausted.
(4) The oil chamber of the oil conservator
is poorly sealed (the diaphragm or capsule is broken, the bellows is cracked,
etc.), so that the oil level enters the diaphragm or capsule, and the oil level
is low: overhaul the oil conservator.
(5) The transformer leaks seriously,
causing the oil level to be low: deal with the leak point and refill the oil.
(1) Open the vent hole of the oil
conservator or oil tank to break the vacuum environment.
(2) When the oil in the oil storage tank
does not need to be discharged, the butterfly valve of the gas pipeline can be
closed, and only the oil in the oil tank can be discharged. (When overhauling
the part below the oil conservator, such as bushing replacement work)
(3) The amount of oil discharged should be
calculated according to the scope of maintenance. (Replacement of bushing,
pressure relief valve, vacuum butterfly valve, and overall transformer overhaul
have different oil discharge volumes)
(4) Pay attention to the temperature and
humidity when discharging oil, and the oil discharge should be carried out at a
relative humidity of ≤75%.
Note: Be sure to open the vent plug before
draining oil
(1) The main body of the transformer should be vacuumed before large-scale oil filling, and a connecting pipe should be installed between the tap changer and the main body before vacuuming. (If the gas and oil conservator cannot be evacuated, the butterfly valve of the oil conservator should be closed)
(2) Vacuum, the vacuum value should reach
133pa, and keep it for a certain period of time (110 kV for 4 hours, 220 kV for
8 hours). Vacuuming is strictly prohibited in rainy and foggy weather such as
humidity greater than 75%.
(3) After the vacuum degree is maintained
for a certain period of time, start oil injection. Oil injection should be from
the oil inlet valve at the bottom of the main transformer oil tank, and stop
oil injection when the injection distance is 200mm-300mm from the top of the
tank.
(1) When the transformer is filled with oil after vacuum oil filling, it needs to be injected through the oil filling pipe of the oil conservator, and it is strictly forbidden to inject from the valve of the lower oil tank.
(2) For the vent holes such as the casing
riser seat and the upper pipe of the radiator, the exhaust should be exhausted
several times until exhausted.
(3) The gas inside the oil chamber of the
oil conservator should be exhausted to prevent false oil level. For oil
conservators with different structures, the exhaust methods are different, but
in the end the core inspection principle: oil coming out of the exhaust hole
means that the gas is discharged cleanly.
(1) Personnel working at heights must pass
the physical examination and obtain a special operation certificate before they
can engage in operations at heights.
(2) Personnel working at heights should use
seat belts correctly, and seat belts are strictly prohibited from being hung
low and high.
(3) Special personnel should be assigned to
monitor the work at heights.
(4) Corresponding fire-fighting equipment
should be equipped when oil operations are carried out on site.
If transformer oil during long time operation or new transformer oil before filling into power transformer, it requires vacuum oil filtration. This is in order to remove moisture, gases, dust, particulate matters, metals, etc. from transformer oil which may affect the insulating performance of transformer oil. With PureTech designed and manufactured Double Stage Vacuum Transformer Oil Purifier, you can easily and effectively remove previous contaminants from transformer oil, and maintain the good insulation performance of transformer oil. Model DVOP Double stage vacuum Transformer Oil Purifier is especially suitable for 110kv and above transformers, while Model VOP single stage vacuum transformer oil purifier is suitable for low voltage transformers like 33kv, 66kv. Please contact us for more information of vacuum transformer oil purifier.