Which parts of the transformer may have
high heat during operation? What is the reason? How to judge?
There are various types of transformer
failures during operation, which pose a serious threat to the transformer.
Several major components may have local high heat. In addition to the hottest
spot of the coil during normal operation, we talk about the local high heat
problem under abnormal conditions of each part.
1. The tap changer is in poor contact
The local high temperature caused by the
poor contact of the tap changer is a relatively common problem at present. In
fact, since the transformer is a static electrical appliance, in addition to
the hidden dangers of the iron core and coil caused by poor manufacturing
quality, as long as attention is paid during operation, the transformer iron
core and coil are faulty. Still relatively few. But the tap-changer is switched
frequently, and the chance of problems may be more.
The heating of the tap changer is mainly
caused by the poor contact, which increases the contact resistance. Since the
loss is equal to I2R, if R is large, the loss will be large and the heat will
be severe. This is especially likely to happen after reverse splits and when
the transformer is overloaded. Poor contact can be caused by:
(1) The contact point pressure is not
enough;
(2) There is sludge accumulation in the
contact of the switch, so that there is a layer of sludge film between the
dynamic and static contacts;
(3) The contact surface is small so that
the contacts are melted;
(4) The positioning indication and the
contact position of the switch are not quite aligned (the positioning point has
been indicated correctly but the close contact point of the switch has moved
away);
(5) Several contact rings of DW type drum
tap changer are not in contact with the contact column at the same time, etc.
The local high temperature of the tap changer
has endangered the safe operation of the transformer, some caused the
transformer to burn out, and some caused the rapid deterioration of the oil
quality, which forced emergency shutdown for maintenance.
So how to judge the poor contact of the tap
changer during operation? This kind of fault is most likely to occur after
overhaul or after switching the split head, and the contact surface may also be
burned after the traversing fault. The current chromatographic analysis
basically correctly judges it. When the chromatogram determines that the bare
metal is overheated, the transformer can be stopped, and the DC resistance of
the three-phase tap can be measured to determine the contact condition of the
tap changer. During chemical analysis, the flash point drops rapidly, it may
also be a poor contact of the tap changer. High pressure testing,
chromatography and chemical analysis can all monitor it from different angles.
In addition, strengthen the observation during operation, especially the
frequent movements of light gas may also be caused by poor contact.
2. Short circuit between turns of coil
The so-called inter-turn short circuit is
the insulation damage between several adjacent turns. This will create a closed
short-circuit loop and, at the same time, reduce the number of turns in the
coil for that phase. The short-circuit current induced by the alternating
magnetic flux flows in the short-circuit loop, which will generate high heat
and may cause the transformer to burn out.
According to statistics, transformer damage
caused by inter-turn short circuit is more, accounting for about 77% to 80% of
the total damage. Therefore, enough attention should be paid to this issue.
There are many reasons for the short
circuit between turns, such as:
(1) Mechanical damage to insulation caused
by beating, bending, pressing and other processes during coil manufacturing, or
some copper and iron puncture insulation leaves hidden dangers;
(2) After running for a long time, the
insulation ages and becomes brittle, so that the wires are connected;
(3) The local high temperature during
operation causes the insulation to age rapidly (these local high temperatures
such as "dead corners" of oil flow, blockage of oil passages, etc.);
(4) In the case of a penetrating short
circuit, the axial or radial displacement of some turns under the action of
electrodynamic force will cause the insulation to wear out;
(5) The oil level of the transformer drops,
so that the coil is exposed to lose cooling;
(6) Long-term overload operation and
unscientific temperature control make the copper wire temperature too high and
the insulation becomes brittle quickly. Of course, the real development of
inter-turn short circuit often occurs after over-voltage and over-current.
Less serious inter-turn short circuits are
difficult to find, even by conventional insulation tests, but chromatographic
analysis is more sensitive and may be found. The more serious inter-turn short
circuit can also be found during operation. Due to severe heating, the oil
temperature rises, and the current increases to some extent;
Light gas action. It is particularly worth
mentioning that when the short-circuit turns are hot, the oil is like boiling,
and the sound of "gurgling" can be heard next to the transformer.
Before the development of heavy gas operation, take oil samples for testing,
the oil quality will change, and chromatographic analysis is an obvious fault,
which is easy to confirm, and gas sample analysis can also find the problem.
A stopped transformer can sometimes find
inter-turn short circuits from the ratio and DC resistance tests.
3. There is a short circuit in the iron
core silicon steel sheet
The iron core is made of silicon steel
sheets that are insulated from each other. Due to external force damage or
insulation aging and other reasons, the insulation of the paint skin between
the silicon steel sheets is damaged, which will increase the eddy current,
cause local overheating, and even melt in severe cases, which is the so-called
"iron core fire".
In addition, the insulation damage of the
feedthrough screw is also one of the reasons for the circulation. The
feedthrough screw generally has an insulating sleeve to insulate it from the
silicon steel sheet, and there are insulating washers at both ends to insulate
it from the clip. The above-mentioned insulation damage may be caused by the
damage to the insulation when the nut is tightened or the eddy current heating
in the screw itself, which often makes the insulation brittle at high
temperatures. If the insulation of several screws is damaged, a short circuit
will be formed between the screws and the iron core, and the circulating
current will flow through, causing the iron core to be partially overheated and
damaged.
Similar to the above-mentioned
short-circuit circuit, if the grounding of the transformer iron core silicon
steel sheet is incorrectly installed (for example, there are several artificial
grounding points, or the iron core is grounded at several points for some
reason), it may also occur. This will cause circulation, local overheating and
lead to serious accidents.
What will happen to the local heating of the iron core during operation? According to the operating experience, if there is a slight local overheating, the oil temperature of the transformer cannot even be observed, and the protection will not act, because the gas generated by the decomposition of the oil is dissolved in the oil at this time. went. If the iron core is overheated locally, the oil temperature will rise, the light gas will operate frequently, flammable gas will be precipitated, the flash point of the oil will drop (this is a unique phenomenon in the oil deterioration process in the transformer), and the oil color will become darker. And may smell burnt. In more serious cases, heavy gas will act.
The phenomenon of short circuit in the iron
core can be found by chromatographic analysis. After the transformer is
stopped, it can also be used to measure the no-load loss (the no-load loss is
increased compared with the original when there is a short circuit), the
insulation resistance (such as the through-core screw to the iron core) and
other tests to find out initially, and then hang the core to find the fault
point.
For the parts and causes of high heat in
the transformer, only the main and possible points have been mentioned above.
Of course, there are other parts and causes, such as joint heating (the welding
place between the lead and the coil, the lead and the middle conductor of the
bushing, etc.). The nut connection of the rod, the internal welding head of the
coil, etc.); the insulation of the pressure ring screw is damaged or the
pressure ring touches the iron core to cause a circulating current; a screw or
iron piece causes overheating through a large amount of magnetic leakage and a
large eddy current.
Transformer oil performs important role in power transformers, it works as cooling and insulation material. Therefore, the properties of transformer oil must be ensured by transformer oil treatment, that is, transformer oil filtration, vacuum dehydration and transformer oil degassing, as well as Transformer Oil Regeneration.
More information about Transformer Oil Filtration Machines, and power transformer maintenance equipment, please don't hesitate to contact us.
PureTech Oil Filtration
web: www.cqpuretech.com
Tel:+8617815389416
Email: sales@cqpuretech.com
Name: PURETECH
Mobile:+86 17815389416
Tel:+86 17815389416
Whatsapp:+8617815389416
Email:sales@cqpuretech.com
Add:1 Xinmao Road, Beibei district, Chongqing, China